Monday, June 15, 2015

Save space with a RB series temperature controller that gives outstanding control capability and comprehensive functions incorporated into a slim body case.
  • Panel space saving : 60mm depth (RB100 : 63mm depth)
  • Easy maintenance Plug-in
  • Easy-to-read with large 11-segment LCD display
  • Store up to 4 Set Values
  • Numerous inputs and outputs (Option)
  • Calculates optimum PID values to stabilize control faster than ever
  • Sampling 0.25sec
  • Easy Fine tuning with 6-level of control response adjustment
  • Startup tuning
  • Easy parameter setup via USB loader port (Loader communication)



Input
a)Temperature input group
Thermocouple : K, J, E, T, R, S, B, N (JIS/IEC), PLII (NBS), W5Re/W26Re (ASTM)
RTD : Pt100 (JIS/IEC), JPt100 (JIS) · 3-wire system
b)Voltage/Current input group
Voltage input (Input impedance : Approx. 1MW)
0 to 1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
Current input (Input impedance : 250W)
4 to 20mA DC, 0 to 20mA DC
*For current input, connect is a 250W shunt resistor to the input terminals. Model code : KD100-55
*Inputs is selectable within each group.
Sampling time0.25 sec
Measuring accuracy
Input TypeRangeAccuracy
K, J, T, E *1Lower than -100°C(-148°F)±(2.0°C[3.6°F] + 1digit)
-100 to 500°C(-148 to 932°F)±(1.0°C[1.8°F] + 1digit)
500°C(932°F) or higher±(0.2% of Reading + 1digit)
N, R, S, PLII *2
W5Re/W26Re
Lower than 0°C(-32°F)±(4.0°C[7.2°F] + 1digit)
0 to 1000°C(32 to 1832°F)±(2.0°C[3.6°F] + 1digit)
1000°C(1832°F) or higher±(0.2% of Reading + 1digit)
BLower than 400°C(752°F)±(70°C[126°F] + 1digit)
400 to 1000°C(752 to 1832°F)±(2°C[3.6°F] + 1digit)
1000°C(1832°F) or higher±(0.2% of Reading + 1digit)
Pt100, JPt100Lower than 200°C(752°F)±(0.4°C[0.7°F] + 1digit)
200°C(392°F) or higher±(0.2% of Reading + 1digit)
Voltage/Current-span to +span±(0.2% of span + 1digit)
*1:Accuracy is not guaranteed for less than -100°C(-148°F)
*2:Accuracy is not guaranteed for less than 400°C(752°F) for input type R, S, B and W5Re/W26Re.
Influence of ambient temperaturea) Temperature input : ±0.06°C/°C [at 5 to 40°C]
b) Voltage/Current input group : ±0.06% of span/°C [at 5 to 40°C]
Close horizontal mounting error±2°C(3.6°F) [Less than -100°C(-146°F) input :±3.5°C(6.3°F)]
Control method
a)PID control with autotuning
P, PI, PD, ON/OFF control selectable
Direct action/Reverse action is selectable
b)Heat/Cool type PID control with autotuning
Control outputRelay contact output, Form a contact, 250V AC 3A (Resistive load)
Voltage pulse output, 0/12V DC
Current output 4 to 20mA DC, 0 to 20mA DC
Voltage output, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
SSR (Triac) output Rated current : 0.5A
Open collector output (Sink type)
Communication
(Optional)
RS-485 (ANSI X3.28 sub-category 2.5A4[RKC standard], MODBUS-RTU)
Standard functionPV bias
Digital filter
Ramp-to-setpoinst
SV step function : Number of SV : 4 points (Default : 1 points)
Timer function
Loader communication (Communication converter COM-K and software WinUCI for RB series and a Windows XP PC are necessary)
Easy Fine tuning with 6-level of control response adjustment
Optional functionEvent (Alarm) function : Up to 4 poinsts
Control loop break alarm (LBA)
Heater break alarm (HBA)
Analog retransmission output
Digital input : 2points

Please contact us: (+84) 968-966-992

Phiên bản Tiếng Việt của "RKC Digital Temperature Controller RB100, RB400, RB500, RB700, RB900"

0 comments: